The ZN65A-12/T3150-40 indoor vacuum circuit breaker is produced by our company based on the latest technologies at home and abroad. Its rated short-circuit breaking current is 40kA.
In the type test of circuit breakers for power distribution, the breaking number of full capacity for this vacuum circuit breaker reaches 50 and its mechanical life is up to 60,000 times. This switching device has also passed the type test of contact breakers. The DC component accounts for more than 70% of the non-symmetrical breaking current.
Simple in structure and easy to maintain, this indoor vacuum circuit breaker features stable and reliable operation. It is equipped with a spring energy storage type operating mechanism.
Application
With excellent breaking performance and long mechanical life, this vacuum circuit breaker can be used for the control and protection of outlet of small generator, steelmaking electric furnace, and other electrical equipment.
Ordinary Type | Altitude: <1,000m |
Ambient Temperature: -25℃~ 40℃ (-40℃ is fine for special product) | |
Relative Humidity: Daily average≤95%, monthly average≤90% | |
Earthquake Intensity<8degree, no fire, explosion, corrosive gases, or severe shaking | |
Suitable-for-all-working-conditions Type | The product can be used in places where there is condensation and filth. |
Item | Unit | Value |
Rated Voltage | kV | 12 |
Rated Current | A | 1600 2000 2500 3150 |
Rated Short-circuit Breaking Current | kA | 40 |
Rated Peak Withstand Current | kA | 100 |
Rated Short-time Withstand Current | kA | 40 |
Rated Short-circuit Closing Current (peak value) | kA | 100 |
Rated Short Circuit Duration | s | 4 |
Rated Short-circuit Current Breaking Times | times | 50 |
Rated Operating Sequence | O-0.3s-CO-180s-CO | |
Rated Frequency | Hz | 50 |
Lightning Impulse Withstand Voltage (Peak Value) | kV | 75 |
1min Power Frequency Withstand Voltage | kV | 42 |
Closing Time | ms | 45-85(47±7) |
Opening Time | ms | 45-85(52±7) |
Breaking Time | ms | ≤ 80 |
Mechanical Life | times | 60,000 |
Rated Power of the Energy Storage Motor | W | 200 |
Rated Voltage of the Energy Storage Motor | V | AC, DC 110, 220 |
Energy Storage Time | s | ≤15 |
Rated Voltage of the Closing and Opening Electromagnet | V | AC, DC 110.220 |
Rated Current of the Auxiliary Switch | A | AC10, DC5 |