The ZN63A-12 indoor vacuum circuit breaker is a switching device with the rated voltage of AC 12kV and the rated frequency of 50Hz. It is suitable to work as the control and protection equipment in power plants, industrial and mining enterprises, as well as other places. It is applicable to occasions requiring frequent operations.
This indoor vacuum circuit breaker has features of simple structure, reliable performance, easy installation and maintenance, as well as long service life. It adopts a spring energy storage type operating mechanism, which can be manually or electrically (AC or DC) operated.
Composite insulation is adopted by this high voltage circuit breaker. The vacuum arc chute is installed inside an insulation cylinder, so it is less subjected to external environment impact and mechanical damage and has a strong anti-pollution ability.
Ambient Temperature | Upper limit: 4 0 ℃ |
Lower limit: -25 ℃ | |
Ambient Humidity | Daily average relative humidity≤ 95% |
Monthly average relative humidity≤ 90% | |
Daily average saturated vapor pressure≤ 2.2×103MPa | |
Monthly average saturated vapor pressure≤ 1.8×103MPa | |
Altitude | ≤1000m |
Earthquake Intensity | ≤8degree |
Place of Use | No risk of fire or explosion, no chemical corrosion, no severe shaking |
No. | Item | Unit | 630-25 | 1250-31.5 | 2500-31.5 | 3150-40 | 4000-40 | 4000-50 |
1 | Rated Voltage | KV | 12 | |||||
2 | Rated Impulse Withstand Voltage (Peak) | KV | 75 | |||||
3 | Rated Short-time Withstand Voltage (1min) | KV | 42 | |||||
4 | Rated Frequency | HZ | 50 | |||||
5 | Rated Current | A | 630 | 1250 | 2500 | 3150 | 4000 | 4000 |
6 | Rated Short-circuit Breaking Current | KA | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Rated Short-circuit Closing Current | KA | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Rated Peak Withstand Current | KA | 63 | 80 | 80 | 100 | 100 | 125 |
9 | Rated Short-time Withstand Current | KA | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
10 | Rated Operating Sequence | O-0.3s-CO-180s-CO | O-180s -CO-180s-CO | |||||
11 | Rated Short-circuit Current Breaking Times | times | 50 | 50 | 50 | 20 | 30 | 20 |
12 | Rated Current Breaking Times | times | 20000 | 10000 | ||||
13 | Rated Breaking Current of Single or Back-to-back Capacitor Bank | A | 630/400 | |||||
14 | Mechanical Life | times | 20000 | 10000 | ||||
15 | Power of the Energy Storage Motor | W | 70 | |||||
16 | Energy Storage Time | s | ≤ 10 | |||||
17 | Voltage of the Energy Storage Motor | V | AC/DC, 220/110 | |||||
18 | Rated Short Circuit Duration | s | 4 |
Note: When the rated current reaches 4,000A, forced air cooling is required.
No. | Item | Unit | 630-25 | 1250-31.5 | 2500-31.5 | 3150-40 | 4000-40 | 4000-50 |
1 | Contact Travel | mm | 11±1 | |||||
2 | Contact Overtravel | mm | 3.5±0.5 | |||||
3 | Phases Center Distance | mm | 210±0.5 | 210±0.5 | 275±0.5 | 275±0.5 | 275±0.5 | 275±0.5 |
4 | Non-synchronization of the Closing and Opening of the Three Phases | ms | ≤ 2 | |||||
5 | Contact Closing Bounce Time | ms | ≤2 | ≤2 | ≤2 | ≤3 | ≤2 | ≤2 |
6 | Opening time | ms | 20~60 | |||||
7 | Closing Time | ms | 35~100 | 35~100 | 35~100 | 30~70 | 30~70 | 30~70 |
8 | Average Opening Speed | m/s | 0.8~1.3 | |||||
9 | Average Closing Speed | m/s | 0.5~0.9 | |||||
10 | Conductive Loop Resistance of Each Phase | µ Ω | ≤50 | ≤45 | ≤25 | ≤25 | ≤25 | ≤25 |
We are a professional indoor vacuum circuit breaker manufacturer and supplier in China. We provide various types of products such as high voltage vacuum contactor, gas insulated switchgear, low voltage distribution board, and air circuit breaker.