Home ZN63A-12 Indoor Vacuum Circuit Breaker

ZN63A-12 Indoor Vacuum Circuit Breaker

The ZN63A-12 indoor vacuum circuit breaker is a switching device with the rated voltage of AC 12kV and the rated frequency of 50Hz. It is suitable to work as the control and protection equipment in power plants, industrial and mining enterprises, as well as other places. It is applicable to occasions requiring frequent operations.

ZN63A-12 Indoor Vacuum Circuit Breaker

This indoor vacuum circuit breaker has features of simple structure, reliable performance, easy installation and maintenance, as well as long service life. It adopts a spring energy storage type operating mechanism, which can be manually or electrically (AC or DC) operated.


Composite insulation is adopted by this high voltage circuit breaker. The vacuum arc chute is installed inside an insulation cylinder, so it is less subjected to external environment impact and mechanical damage and has a strong anti-pollution ability.


Conditions of Use Environment
Ambient Temperature Upper limit: 4 0 ℃
Lower limit: -25 ℃
Ambient Humidity Daily average relative humidity≤ 95%
Monthly average relative humidity≤ 90%
Daily average saturated vapor pressure≤ 2.2×103MPa
Monthly average saturated vapor pressure≤ 1.8×103MPa
Altitude ≤1000m
Earthquake Intensity ≤8degree
Place of Use No risk of fire or explosion, no chemical corrosion, no severe shaking

1. Main Technical Parameters
No. ItemUnit 630-25 1250-31.5 2500-31.5 3150-40 4000-40 4000-50
1 Rated VoltageKV 12
2 Rated Impulse Withstand Voltage (Peak) KV 75
3 Rated Short-time Withstand Voltage (1min) KV 42
4 Rated FrequencyHZ 50
5 Rated CurrentA 630 1250 2500 3150 4000 4000
6 Rated Short-circuit Breaking CurrentKA 25 31.5 31.5 40 40 50
7 Rated Short-circuit Closing Current KA 63 80 80 100 100 125
8 Rated Peak Withstand Current KA 63 80 80 100 100 125
9 Rated Short-time Withstand CurrentKA 25 31.5 31.5 40 40 50
10 Rated Operating SequenceO-0.3s-CO-180s-CO O-180s -CO-180s-CO
11 Rated Short-circuit Current Breaking Timestimes 50 50 50 20 30 20
12 Rated Current Breaking Timestimes 20000 10000
13 Rated Breaking Current of Single or Back-to-back Capacitor Bank A 630/400
14 Mechanical Lifetimes 20000 10000
15 Power of the Energy Storage MotorW 70
16 Energy Storage Times≤ 10
17 Voltage of the Energy Storage Motor V AC/DC, 220/110
18 Rated Short Circuit Durations 4

Note: When the rated current reaches 4,000A, forced air cooling is required.


2. Technical requirements
No. Item Unit 630-25 1250-31.5 2500-31.5 3150-40 4000-40 4000-50
1 Contact Travel mm 11±1
2 Contact Overtravel mm 3.5±0.5
3 Phases Center Distance mm 210±0.5 210±0.5 275±0.5 275±0.5 275±0.5 275±0.5
4 Non-synchronization of the Closing and Opening of the Three Phases ms ≤ 2
5 Contact Closing Bounce Time ms ≤2 ≤2 ≤2 ≤3 ≤2 ≤2
6 Opening time ms 20~60
7 Closing Time ms 35~100 35~100 35~100 30~70 30~70 30~70
8 Average Opening Speedm/s 0.8~1.3
9 Average Closing Speedm/s 0.5~0.9
10 Conductive Loop Resistance of Each Phase µ Ω ≤50 ≤45 ≤25 ≤25 ≤25 ≤25

We are a professional indoor vacuum circuit breaker manufacturer and supplier in China. We provide various types of products such as high voltage vacuum contactor, gas insulated switchgear, low voltage distribution board, and air circuit breaker.