The indoor SF6 gas insulated current transformer work properly with the ambient temperature between -25℃ and 40℃. It should be installed in a place free from vibration, impact, and jolt.
Rated insulation level | 126/185/450kV |
Rated primary current | 2×200, 2×300, 2×400, 2×500, 2×600, 2×750, 2×1000 A |
Rated secondary current | 5A |
Load power factor | COSΦ=0.8 (lagging) |
Accuracy classes combination | 0.2S/0.5/P/P, 0.2/0.5/P/P, 0.2/P/P/P, 0.5/P/P/P |
Partial discharge level | ≤5pC |
Accuracy class and rated burden corresponding to rated current are shown below:
Rated primary current (A) / Rated secondary current (A) | Measurement class | Protection Class | |||||||
Accuracy | Burden (VA) | Accuracy | Burden (VA) | Accuracy | Burden (VA) | Accuracy | Accuracy limit factor | Burden (VA) | |
2×200/5 | 0.2S | 20 | 0.2 | 20 | 0.5 | 25 | 10P | 10 | 20 |
2×300/5 | 0.2S | 20 | 0.2 | 20 | 0.5 | 25 | 10P | 15 | 30 |
2×400/5 | 0.2S | 20 | 0.2 | 20 | 0.5 | 25 | 10P or 5P | 15 | 30 |
2×500/5 | 0.2S | 25 | 0.2 | 25 | 0.5 | 30 | 10P or 5P | 15 | 40 |
2×600/5 | 0.2S | 25 | 0.2 | 25 | 0.5 | 30 | 10P or 5P | 20 | 40 |
2×750/5 | 0.2S | 30 | 0.2 | 30 | 0.5 | 40 | 10P or 5P | 20 | 40 |
2×1000/5 | 0.2S | 30 | 0.2 | 30 | 0.5 | 40 | 10P or 5P | 20 | 40 |
Note: 1. The parameters in the above table are for reference only and they can be customized as per customer requirements.
2. Rated pressure (manometer pressure at 20℃): 0.6MPa
3. Make-up gas pressure (manometer pressure at 20℃): 0.5MPa
4. Annual leakage rate of SF6 is less than 0.5%.
Related Names
Current Metering | High Voltage Current Transformer | Measuring Current Transformer | Protective Current Transformer