Home Indoor SF6 Gas Insulated Current Transformer

Indoor SF6 Gas Insulated Current Transformer

The indoor SF6 gas insulated current transformer work properly with the ambient temperature between -25℃ and 40℃. It should be installed in a place free from vibration, impact, and jolt.


Technical Parameters of Indoor SF6 Gas Insulated Current Transformer
Rated insulation level 126/185/450kV
Rated primary current 2×200, 2×300, 2×400, 2×500, 2×600, 2×750, 2×1000 A
Rated secondary current 5A
Load power factor COSΦ=0.8 (lagging)
Accuracy classes combination 0.2S/0.5/P/P, 0.2/0.5/P/P, 0.2/P/P/P, 0.5/P/P/P
Partial discharge level ≤5pC

Accuracy class and rated burden corresponding to rated current are shown below:


Rated primary current (A) / Rated secondary current (A) Measurement class Protection Class
Accuracy Burden (VA) Accuracy Burden (VA) Accuracy Burden (VA) Accuracy Accuracy limit factor Burden (VA)
2×200/5 0.2S 20 0.2 20 0.5 25 10P 10 20
2×300/5 0.2S 20 0.2 20 0.5 25 10P 15 30
2×400/5 0.2S 20 0.2 20 0.5 25 10P or 5P 15 30
2×500/5 0.2S 25 0.2 25 0.5 30 10P or 5P 15 40
2×600/5 0.2S 25 0.2 25 0.5 30 10P or 5P 20 40
2×750/5 0.2S 30 0.2 30 0.5 40 10P or 5P 20 40
2×1000/5 0.2S 30 0.2 30 0.5 40 10P or 5P 20 40

Note: 1. The parameters in the above table are for reference only and they can be customized as per customer requirements.
2. Rated pressure (manometer pressure at 20℃): 0.6MPa
3. Make-up gas pressure (manometer pressure at 20℃): 0.5MPa
4. Annual leakage rate of SF6 is less than 0.5%.

Indoor SF6 Gas Insulated Current Transformer

Related Names
Current Metering | High Voltage Current Transformer | Measuring Current Transformer | Protective Current Transformer