Product Overview
Generally, the TSC2 series fuse cutout contains load type and common type in light of structure difference. It can be divided into 12kV, 24kVand 36kV types based on applicable rated voltage.
Model | TSC2-12 | TSC2-20 | TSC2-36 |
Rated voltage | 12kV | 24kV | 36kV |
Rated frequency | 50Hz | ||
Rated current | 100A, 200A, 300A (isolating switch blade) | 100A | 100A |
Power frequency withstand voltage (phase to phase/between interrupting points) | 50kV/60kV | 70kV/80kV | 100kV/110kV |
Lightning impulse withstand voltage (phase to phase/between interrupting points) | 110kV/125kV | 150kV/165kV | 195kV/210kV |
Rated switching off current | 12.5KA, 16KA (each fuse tube enables short circuit switching off for two times.) | 12.5KA | 10KA |
Mechanical life | 2000 times | ||
Creepage distance | ≤31mm/kV (Large creepage distance is also available.) | ||
Cut-off load current | 100A/200A | ||
Weight | 6.5kg | 12kg | 16kg |
Components of the Fuse Cutout
1. This fused cut out can be fitted with cast copper parallel-groove connector. (optional configuration)
2. Stainless steel protective cover
3. We equip the silver-to-silver top contact of our fuse cutout with stainless steel compression spring.
4. Brass pull ring
5. To prevent fuse tube from switch-off shaking, a high-strength silver coated cast copper lug is used.
6. The stainless steel spring plate of this fuse cut out facilitates prompt fuse wire drawing.
7. Dual current diversion is achieved thanks to silver-to-silver lower contact.
8. High-strength bird-proof insulator
9. Stainless steel mounting bracket
10. Arc-extinguishing chamber (optional configuration)
11. Auxiliary conducting loop
12. Our fuse cutout is available with anti-UV epoxy tube. (optional configuration)
Dimensions of the Fuse Cutout