The XGN15-12 ring main unit is a kind of compact and extensible metal-enclosed switchgear which uses SF6 circuit breaker as the main switch and air for insulation. It is characterized by simple structure, convenient installation, flexible operation, and reliable interlocking. It can be used in the power systems with the rated frequency of 50Hz or 60 Hz and the rated voltage of 12kV AC.
This ring main unit is widely used at the end of industrial and residential cable ring network power supply system in the airport, subway, hospital, stadium, shopping mall, industrial and mining enterprises, and many other places.
Technical ParametersItem | Load switch | Load switch fuse | |
Rated voltage KV | 12 | ||
Rated current A | 630 | 125 | |
Busbar rated current A | 630 | ||
Transfer current breaking capacity A | 1700 | ||
Rated short circuit making current KA | 50 | Depends on the fuse | |
Rated short-circuit breaking current KA | 50 | Depends on the fuse | |
Rated thermal current (3s) KA | 20 | ||
Rated dynamic stability current KA | 50 | ||
Mechanical life times | Load switch | 5000 | |
Earthing switch | 2000 | ||
Rated filling pressure MPa | 0.04 | ||
Ambient temperature | -10°~ 40° | ||
Altitude | ≤1000m | ||
Dimensions (W×H×D) | 375×1850×940 500×1850×940 (Metering cabinet) |
Related Names