The VTK-12/T3150-40(F) and VTK-12/5000-50(F) indoor vacuum generator circuit breakers, which are independently developed by our company, meet the demanding requirements of protecting the vacuum generator outlet. They have the following characteristics.
1. Our product has passed a full set of type tests in strict accordance with the GB/T 14824 -1993 "General Technical Conditions of the Generator Breaker" in Xi'an High Voltage Apparatus Research Institute;
2. It is equipped with a domestic arc chute with high cost-performance;
3. The spring operating mechanism adopted is reasonably designed and it has complete operating functions, high reliability, and little maintenance. It is integrated together with the circuit breaking device;
4. Our product has high breaking capacity, high closing stability, as well as high dynamic and thermal stability;
5. The copper outgoing line, dual soft connection conductive parts, and special cooling rack perfectly solve the heat problem caused by long-term operation at large current;
6. This VTK-12KV indoor vacuum generator circuit breaker is suitable for installation on the XGN-12 fixed type and KYN28A-12 withdrawable type switchgears.
No. | Item | Unit | Value | |||
1 | Rated voltage | kV | 12 | |||
2 | Rated frequency | Hz | 50 | |||
3 | 1min Power frequency withstand voltage (rms) | phase to earth, phase to phase | kV | 42 | ||
between fractures | 50 | |||||
Lightning impulse withstand voltage (peak) | phase to earth, phase to phase | 75 | ||||
between fractures | 85 | |||||
4 | Standard value of the system source's expected transient recovery voltage | Peak voltage | kV | 22 | ||
Reference time | μs | 5.5 | ||||
Rate of rise | kV/μs | 4 | ||||
5 | Rated current | A | 3500 | 5000 | ||
6 | Rated short-circuit breaking current | kA | 40 | 50 | ||
7 | Rated operating sequence | Close open-30min-close open | ||||
8 | Rated short circuit making current (peak) | kA | 110 | 137 | ||
9 | Rated dynamic current (peak) | 110 | 137 | |||
10 | Rated thermal current | 40 | 50 | |||
11 | Rated thermal stabilization time | s | 4 | 2 | ||
12 | Times of breaking rated short-circuit current | times | 8 | |||
13 | DC component of the rated short-circuit breaking current | ≥75% (80%) | ||||
14 | Times of breaking rated load current | times | 50 | |||
15 | Rated short-circuit stepping-out breaking current | kA | 20 | 25 | ||
16 | Mechanical life | times | 10000 |
Related Names
Electrical Circuit Breaker | Ground Fault Circuit Breaker | Mechanical Breaker