1. Product Overview
The BTK-126kV/252kV transformer neutral point protection device mainly comprises the neutral point disconnector, discharge gap protector, zinc oxide lightning arrester, and current transformer. It plays a protective role when there is lightning overvoltage, operation overvoltage and temporary overvoltage in the transformer neutral point.
To facilitate equipment layout, we can design and produce extra T-shaped or gate type bracket to assemble various parts of the transformer neutral point protection device together.
2. Features
a. Fast and convenient to assemble;
b. The rod gap device is a separate part. It is made of stainless steel and the gap distance is easy to adjust;
c. After the user specifies the model of arrestor and current transformer, installation holes will be correctly reserved;
d. The adopted hot dip galvanized steel bracket is strong and anti-corrosion;
e. The CS17IV manual mechanism is adopted. It is equipped with a stainless steel case. The whole structure has good sealing performance as well as strong resistance to water, dust, and rust. The new type DSW4 electromagnetic lock can be configured.
f. The CJTKB electric mechanism is used. With a stainless steel case, it is beautiful in appearance, dustproof, waterproof, and anti-corrosion. It can meet the requirements of interlocking. The secondary components are of high quality and from domestic famous enterprises or joint ventures.
Gap rated voltage (kV) | System rated voltage (kV) | Electrode gap range (mm) | Power frequency discharge voltage range (mm) | Insulator creepage distance (mm) | Transformer capacity (VA) | Antifouling level | Electrodes form |
63 | 126 | 90-135 | 50-63 | 1813 | 20 | Ⅲ | Hemispherical |
63 | 126 | 90-135 | 50-63 | 2248 | 20 | Ⅳ | Hemispherical |
126 | 252 | 280-330 | 100-127 | 3150 | 20 | Ⅲ | Hemispherical |
126 | 252 | 280-330 | 100-127 | 3906 | 20 | Ⅳ | Hemispherical |
Model | GW8/13-72.5I | GW8/13-126I | |
Rated voltage kV | 72.5 | 126 | |
Rated current A | 630,1250 | ||
Rated peak withstand current kA | 63,100 | ||
Rated short-time withstand current kA | 25,40 | ||
Rated short-circuit duration s | 4,4 | ||
Rated short-time power frequency withstand voltage (rms) kV | 178/200* | 230/260* | |
Rated lightning impulse withstand voltage (peak) kV | 282/318* | 550/625* | |
Rated terminal static mechanical load N | Horizontal longitudinal | 1000 | 1250 |
Horizontal transverse | 750 | 750 | |
Vertical | 1000 | 1000 | |
Mechanical life | 3000 times | ||
Opening and closing time of the attached electric mechanism s | 5±1 | ||
Weight kg | 120 | 155 |
Note: For the data marked with "*", the number before "/" is the parameter value measured at an altitude of 2000 m and the number after "/" is the parameter value measured at an altitude of 1000 m
System nominal voltage kV | Lightning arrester model | Lightning arrester rated voltage kV | DC 1mA reference voltage ≥kV | Residual voltage under 8/20μs lightning impulse current ≤kV | 2ms Square wave A | 4/10μs large current kA |
126 | YH1.5W-60/144 | 60 | 86 | 144 | 400 | 10(65) |
126 | YH1.5W-72/186 | 72 | 105 | 186 | 400 | 10(65) |
126 | YH1.5W-73/200 | 73 | 107 | 200 | 400 | 10(65) |
252 | YH1.5W-144/320 | 144 | 205 | 320 | 400 | 10(65) |
4. Service and Installation Conditions
Ambient temperature: -50℃~ 50℃;
Altitude: ≤ 2000m;
Wind pressure: ≤ 700Pa;
Ice thickness: ≤ 20 mm;
Pollution class: class III and IV;
Seismic intensity: ≤ Mercalli IX.
There should be no inflammable, explosive, corrosive materials or violent vibration in the mounting site.