The series gap metal oxide lightning arrester is an important lightning protection device in AC transmission lines. When the tower arm potential rises, the series gap discharges and its lightning volt-second characteristic is lower than that of insulator, which can prevent insulator flashover and line trip.
Model | Rated voltage | Maximum continuous operating voltage | Sparkover voltage | Residual voltage under 8/20 μs lightning impulse | 2000μs square wave current impulse withstand | 4/10μs high current impulse withstand | |
Power frequency ≥ | 1.2/50 μs lightning impulse ≤ | ||||||
kV (RMS) | kV (RMS) | kV (RMS) | kV (peak) | kV (peak) | A (peak) | kA (peak) | |
Y5 C -3 | 3 | 2.55 | 5.0 | 7.8 | 9 | 1 00 | 65 |
Y5 C -6 | 6 | 5.1 | 10.0 | 15.5 | 18 | 1 00 | 65 |
Y5 C -9 | 9 | 7.65 | 16.5 | 24.5 | 27 | 1 00 | 65 |
Y5C-10 | 10 | 8.4 | 18.0 | 27.2 | 30 | 100 | 65 |
Y5 C -12 | 12 | 10.2 | 21.0 | 32.6 | 36 | 1 00 | 65 |
Y5 C -15 | 15 | 12.7 | 25.0 | 38.8 | 45 | 1 00 | 65 |
Y5 C -18 | 18 | 15.3 | 31.0 | 48.1 | 54 | 1 00 | 65 |
Y5 C -21 | 21 | 17.0 | 34.0 | 52.7 | 63 | 1 00 | 65 |
Y5 C -24 | 24 | 19.5 | 39.0 | 60.5 | 72 | 1 00 | 65 |
Y5 C -27 | 27 | 22.0 | 45.0 | 69.8 | 81 | 1 00 | 65 |
Y5 C -30 | 30 | 24.4 | 50.0 | 77.5 | 90 | 1 00 | 65 |
Y5 C -33 | 33 | 26.8 | 55.0 | 85.3 | 99 | 1 00 | 65 |
Y5 C -36 | 36 | 29.0 | 60.0 | 93.0 | 108 | 1 00 | 65 |
Y5C-42 | 42 | 34.1 | 70.0 | 108.5 | 126 | 100 | 65 |
Model | Rated voltage | Maximum continuous operating voltage | Sparkover voltage | Residual voltage under 8/20 μs lightning impulse | Line discharge class | 4/10μs high current impulse withstand | |
Power frequency ≥ | 1.2/50 μs lightning impulse ≤ | ||||||
kV (RMS) | kV (RMS) | kV (RMS) | kV (peak) | kV (peak) | kA (peak) | ||
Y10 C -3 | 3 | 2.55 | 9.5 | 7.7 | 9 | 1 | 100 |
Y10 C -6 | 6 | 5.1 | 19.5 | 15.4 | 18 | 1 | 100 |
Y10 C -9 | 9 | 7.65 | 28.5 | 23.1 | 27 | 1 | 100 |
Y10C-10 | 10 | 8.40 | 18.0 | 27.2 | 30 | 1 | 100 |
Y10 C -12 | 12 | 10.2 | 38.0 | 30.8 | 36 | 1 | 100 |
Y10 C -15 | 15 | 12.7 | 47.5 | 38.5 | 45 | 1 | 100 |
Y10 C -18 | 18 | 15.3 | 57.0 | 46.2 | 54 | 1 | 100 |
Y10 C -21 | 21 | 17.0 | 66.5 | 53.9 | 63 | 1 | 100 |
Y10 C -24 | 24 | 19.5 | 76.0 | 61.6 | 72 | 1 | 100 |
Y10 C -27 | 27 | 22.0 | 85.5 | 69.3 | 81 | 1 | 100 |
Y10 C -30 | 30 | 24.4 | 95.0 | 76.5 | 90 | 1 | 100 |
Y10 C -33 | 33 | 26.8 | 104.5 | 84.7 | 99 | 1 | 100 |
Y10 C -36 | 36 | 29.0 | 114.0 | 92.4 | 108 | 1 | 100 |
Y10 C -42 | 42 | 34.0 | 132.3 | 100.1 | 126 | 1 | 100 |
Note:
The product is packed by customary packaging. If customers have special requirements on packaging, we can also meet their needs, but the corresponding packing costs are assumed by the customers.
Related Names
Lightning Protection Device | Power Line Surge Protector | Electrical Surge Arrester