1. Product Overview
The compound surge arrester is used to protect the power systems from being damaged by the atmospheric over-voltage and operating over-voltage. Our product conforms to the standards of GB 11032-2000, JB/T 8952-2005, and IEC 60099-4:2006.
Ambient temperature | -40℃~ 40℃ |
Sunlight intensity | ≤1.1kW/m2 |
Altitude | ≤2000m |
Power supply frequency | 48Hz~62Hz |
The power frequency voltage applied between the terminals for a long term should not exceed the continuous operating voltage of the lightning arrester. | |
Earthquake fortification intensity | Mercalli VII |
Wind velocity | ≤35m/s |
3. Product Structure and Working Principle
The internal core component of our compound surge arrester is the metal oxide varistors with excellent nonlinear volt - ampere characteristic, and there is no clearance between the varistors. The housing is integrally molded, ensuring that the internal components are free from the influence of the external environment.
When overvoltage occurs in the system, the non-linear metal-oxide varistors present low resistance. They absorb the over-voltage energy and make the latter reduce in magnitude greatly, thus protecting the power transmission equipment. When the system runs normally, the non-linear metal-oxide varistors present high resistance, so only a microampere order current passes through the arrester, isolating the system from the earth and ensuring normal operation of the system.
4. Features
a. Excellent anti- contamination feature
b. Unique LV outgoing line structure
c. High operation reliability
d. Good short-circuit withstand capacity
Usys System rated voltage | Product model | Mounting type | Ucov Continuous operating voltage kV | Ures Residual voltage ≤kVP | U1mA DC 1mA reference voltage | Uref Power frequency reference voltage (Resistive current: 1mA) ≥kV | 2ms square wave A | ||
1/4 | 8/20 | 30/60 | |||||||
10 | YH5WZ-17/45×17/45 | Phase - phase | 13.6 | 51.8 | 45 | 38.3 | 25 | 17 | 250 |
Phase - ground | 13.6 | 51.8 | 45 | 38.3 | 24 | 17 | 250 | ||
35 | YH5WZ-51/134 | Phase - phase | 40.8 | 170 | 150 | 134 | 84 | 51 | 400 |
Phase - ground | 40.8 | 170 | 150 | 134 | 73 | 51 | 400 | ||
35 | YH5WZ-51/134×51/150 | Single phase | 40.8 | 154 | 134 | 114 | 73 | 48 | 400 |
Related Names