Home 35~220KV Capacitor Voltage Transformer

35~220KV Capacitor Voltage Transformer

1. Product Overview
The TYD-35~220 series of capacitor voltage transformer is used in the power system with the rated frequency of 50Hz for voltage measurement, electric energy measurement, relay protection, automatic monitoring, and on-gird synchronization. It can also function as a coupling capacitor in power line carrier devices. It complies with the GB/T4703-2007 "Capacitor Voltage Transformer" standard.


2. Product Structures
The product adopts a stacking type structure: the capacitive divider is installed above the electromagnetic unit, which features small floor space. A metal expander is mounted on the capacitive divider to compensate temperature-induced changes in oil level. The electromagnetic unit has an oil-immersed structure and it is enclosed inside the product. An observation window is set on the oil tank for the observation of oil level changes. On the bottom of the oil tank, there is a fully enclosed metal oil drain valve, through which the transformer oil at the lowest part of the tank can be released.

3. Working Conditions
Max. temperature 40℃
Min. temperature -40℃
Altitude ≤1000m (if above 1000m, technical conditions should be discussed by the two parties)
Environmental contamination level Ⅱ, Ⅲ, Ⅳ If the users have special requirements, please specify in the contract.
Earthquake fortification intensity Mercalli IX
Wind velocity ≤35m/s
Installation site Indoors or outdoor


4. Main Features
a. The capacitive voltage divider is installed above the electromagnetic unit. This structure has many advantages, including facilitating transportation and installation, bringing convenience to hand-over test and preventive test, measurement error little affected by temperature.
b. When the 35~220KV capacitor voltage transformer runs at the voltage of 0.8, 0.9, 1.0, 1.2, 1.5 or 1.9 times the rated voltage, the electromagnetic unit will not produce low-frequency resonance. This excels relevant provisions in current national standards.
c. Due to the adoption of a special design, the low-frequency electromagnetic resonance over-voltage is eliminated fundamentally and the insulation level of the electromagnetic unit is improved.
d. Our 35~220KV capacitor voltage transformer has good transient response characteristics and the residual voltage is less than 5% of the initial value. This is superior to current national standards.
e. The lightning arrester at the high voltage side of the intermediate transformer is removed. This improves product operation reliability and reduces the maintenance workload.

35~220KV Capacitor Voltage Transformer
5. Technical Parameters
Model TYD35/√3 -0.01HF TYD35/√3 -0.02HF TYD66/√3 -0.01HF TYD66/√3 -0.02HF TYD110/√3 -0.01H TYD110/√3 -0.02H TYD220/√3 -0.005H TYD220/√3 -0.01H
Max. voltage (kV) 40.5 40.5 72.5 72.5 126 126 252 252
Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Rated capacitance (pF) 10000 20000 10000 20000 10000 20000 5000 10000
Rated voltage factor / time 1.9/8h 1.9/8h 1.9/8h 1.9/8h 1.5/30s 1.5/30s 1.5/30s 1.5/30s
Rated power frequency withstand voltage (kV) 95 95 160 160 200 200 460 460
Rated lightning impulse withstand voltage (kV) 200 200 350 350 480 480 1050 1050
Partial discharge at 1.2Um/√3 (pC) ≤5 ≤5 ≤5 ≤5 ≤5 ≤5 ≤5 ≤5
Secondary winding (1a/1n) Accuracy class Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5 Class 0.2, Class 0.5
Rated output(VA) ≤20 ≤30 ≤30 ≤50 ≤50 ≤150 ≤50 ≤150
Secondary winding (2a/2n) Accuracy class Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P Class 0.5, Class 3P
Rated output(VA) ≤30 ≤50 ≤30 ≤50 ≤50 ≤150 ≤50 ≤150
Remaining windings (da/dn) Accuracy class Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P Class 3P, Class 6P
Rated output(VA) ≤100 ≤100 ≤100 ≤100 ≤100 ≤100 ≤100 ≤100

Note: a. We can provide combinations of different accuracy classes according to the requirements of the users;
b. If the actual product parameter values are no consistent with the ones listed above, please refer to the nameplate.


Typical Product
TYD35/ √ 3-0.01HF
Rated voltage ratio (kV) Classes combination Rated Load (VA)
35/ √ 3:0.1/ √ 3:0.1/3 0.5/3P 30/30
35/ √ 3:0.1/ √ 3:0.1/3 0.5/3P 30/100
35/ √ 3:0.1/ √ 3:0.1/3 0.5/3P 50/100
35/ √ 3:0.1/ √ 3:0.1/ √ 3:0.1/3 0.2/0.5/3P 20/30/100
35/ √ 3:0.1/ √ 3:0.1/ √ 3:0.1/3 0.5/3P/3P 20/30/100
TYD35/ √ 3-0.02HF
Rated voltage ratio (kV) Classes combination Rated Load (VA)
35/ √ 3:0.1/ √ 3:0.1/3 0.5/3P 50/100
35/ √ 3:0.1/ √ 3:0.1/ √ 3:0.1/3 0.2/0.5/3P 30/30/100
35/ √ 3:0.1/ √ 3:0.1/ √ 3:0.1/3 0.2/0.5/3P 30/50/100
35/ √ 3:0.1/ √ 3:0.1/ √ 3:0.1/3 0.2/3P/3P 30/50/100

Related Names
Potential Transformer | Voltage Measuring Instrument | Metering Transformer


Recommended Products
Hot Products